Your browser doesn't support javascript.
Mostrar: 20 | 50 | 100
Resultados 1 - 1 de 1
Filtrar
Añadir filtros

Base de datos
Tipo del documento
Intervalo de año
1.
J Hosp Infect ; 110: 194-200, 2021 Apr.
Artículo en Inglés | MEDLINE | ID: covidwho-1062461

RESUMEN

BACKGROUND: Reducing COVID-19 transmission relies on controlling droplet and aerosol spread. Fluorescein staining reveals microscopic droplets. AIM: To compare the droplet spread in non-laminar and laminar air flow operating theatres. METHODS: A 'cough-generator' was fixed to a theatre trolley at 45°. Fluorescein-stained 'secretions' were projected on to a series of calibrated targets. These were photographed under UV light and 'source detection' software measured droplet splatter size and distance. FINDINGS: The smallest droplet detected was ∼120 µm and the largest ∼24,000 µm. An average of 25,862 spots was detected in the non-laminar theatre, compared with 11,430 in the laminar theatre (56% reduction). The laminar air flow mainly affected the smaller droplets (<1000 µm). The surface area covered with droplets was: 6% at 50 cm, 1% at 2 m, and 0.5% at 3 m in the non-laminar air flow; and 3%, 0.5%, and 0.2% in the laminar air flow, respectively. CONCLUSION: Accurate mapping of droplet spread in clinical environments is possible using fluorescein staining and image analysis. The laminar air flow affected the smaller droplets but had limited effect on larger droplets in our 'aerosol-generating procedure' cough model. Our results indicate that the laminar air flow theatre requires similar post-surgery cleaning to the non-laminar, and staff should consider full personal protective equipment for medium- and high-risk patients.


Asunto(s)
Aerosoles , Microbiología del Aire , COVID-19/prevención & control , COVID-19/transmisión , Transmisión de Enfermedad Infecciosa/estadística & datos numéricos , Ambiente Controlado , Quirófanos/estadística & datos numéricos , Humanos , SARS-CoV-2
SELECCIÓN DE REFERENCIAS
DETALLE DE LA BÚSQUEDA